| King 800/1000/1200AP | |
| Complete protection for internet computers and advanced servers. Features :
|
|
| MODEL | KIN-800AP | KIN-1000AP | KIN-1200AP | |
| CAPACITY | Capacity | 800AV | 1000AV | 1200AV |
| OUTPUT | Voltage (on battery) |
Simulated sine wave at 100V,110V,115V,120V or 220V,230V,240V +/- 5% | ||
| Frequency (on battery) |
50 or 60 Hz +/-0.5Hz | |||
| Voltage Regulation( AVR) | AVR automatically
increase output voltage 15% above input voltage if
-9% to -25% of nominal. AVR decrease output voltage 13% below input voltage if +9% to +25% of nominal |
|||
| Transfer Time | 2 / 4 milliseconds, including detection time | |||
| INPUT | Voltage | 100V,110V,115V,120V or 220V,230V,240V +/- 25% at line input | ||
| Frequency | 50 or 60 Hz +/- 5% (auto sensing) | |||
| PROTECTION & FILTERING |
Spike Protection | 320 Joules, 2ms | ||
| EMI/RFI Filter | 10dB at o.15MHz, 50 dB at 30MHz | |||
| Unit Input | Fuse for overload & short circuit protection | |||
| Overload Protection | UPS automatic power
off if overload exceeds 110% of nominal at 60 seconds and 130% at 3 seconds |
|||
| 10 Base-T Cable Port | Network (UTP, RJ-45) compatible jacks | |||
| Short Circuit | UPS output cut off immediately or input fuse protection | |||
| BATTERY | Type | Sealed, maintenance-free lead acid batteries with 3-6 years typical lifetime | ||
| Typical Recharge Time | 4 hours (to 90% of full capacity) | |||
| Back-up Time (a PC with 15" monitor) |
55 - 65 mins | 60 - 70 mins | 65 - 75 mins | |
| Protection | Automatic self-test, Discharge protection, Replace battery indicator | |||
| PHYSICAL | Net Weight Kg(lbs) | 13.3 (29.3) | 15.0 (33.0) | 15.5 (34.1) |
| Dimension WxDxH (mm) | 130 x 382 x 201 (5.1" x 15" x 7.9") |
|||
| INTERFACE | RS232 | Bi-directional communication port | ||
| ALARM | Battery Back-up | Slow beeping sound (about 0.47 Hz) | ||
| Battery Low | Rapid beeping sound (about 1.824 Hz) | |||
| Overload | Continuously beeping sound | |||
| ENVIRONMENT | Ambient Operation | 3,500 meters max, elevation. 0-95% humidity non-condensing, 0-40 ¢J | ||
| Audible Noise | <40dBA (1 meter from surface) | |||
BACK